Small split hot air type ultra-low NOx gas burner

◎ Flue gas external circulation (FGR), hierarchical combustion technology, combustion air for hot air <200℃, NOx emission ≤50mg/Nm3
◎ Burner power range :175-8000kW
◎ All-electronic proportional adjustment, high adjustment accuracy, High combustion efficiency
◎ Aerodynamic design, low operating noise
◎ Gas pressure protection, air pressure protection
◎ Automatic gas leak detection, dual gas valve set
◎ Safe flame monitoring system
◎ Pre-purge of the furnace
◎ When the burner is shut down, Automatic closing of the damper
◎ Easy installation, debugging and maintenance
◎ Note: Power ≥8000kW, need to be equipped with large split hot air type burner, specific consultation with our technical department

Small split hot air type ultra-low NOx gas burner
  • Product details
Installation Dimensions
 



Models and technical parameters
 
Model Power range (hot air < 150℃)kW Power source
THG7LN/FGR/N 175-1400
380V 3/N/PE 50Hz
THG10.5LN/FGR/N
300-1800 380V 3/N/PE 50Hz
THG14LN/FGR/N
400-2200 380V 3/N/PE 50Hz
THG28-1LN/FGR/N
500-3200 380V 3/N/PE 50Hz
THG28LN/FGR/N
500-3800 380V 3/N/PE 50Hz
THG35LN/FGR/N
900-4300 380V 3/N/PE 50Hz
THG42LN/FGR/N
600-6500 380V 3/N/PE 50Hz
THG56LN/FGR/N
1000-8000 380V 3/N/PE 50Hz



Model L1 L2 L3 A1 A2 A3 A5 фD1 фD2 n-фD3 фD4 D5 7-MD6 H1 H2
THG7LN/FGR/N 480
109 631 370 330 234 374 220 280 8-14 280 DN65 7-M12 207 440
THG10.5LN/FGR/N 480 109 631 370 330 234 374 220 280 8-14 280 DN65 7-M12 207 440
THG14LN/FGR/N 480 130 781 460 410 308 448 279 340 12-14 340 DN80 7-M12 255 520
THG28-1LN/FGR/N 480 130 781 460 410 308 448 279 340 12-14 340 DN80 7-M12 255 520
THG28LN/FGR/N 480 140 790 485 435 333 423 325 390 12-14 390 DN80 7-M12 270 518
THG35LN/FGR/N 580 148 801 538 486 364 468 360 430 16-14 430 DN80 7-M16 284 550
THG42LN/FGR/N 650 166 1007 622 572 454 598 447 510 16-14 510 DN100 7-M16 490 648
THG56LN/FGR/N 650 166 1007 622 572 454 598 447 510 16-14 510 DN100 7-M16 490 648