Gas boiler burner failure and treatment methods
Release date:2023-05-05 15:00:53

Today, we have brought you a gas boiler burner fault and treatment methods, let's go and have a look.

First, the burner ignition rod of the gas boiler does not ignite

The reason:

1. There is carbon slag between the ignition rod and oil pollution.

2. The ignition rod is broken. Humid. There is a leak.

3, the distance between the fire rod is not right, too long or short.

4, the ignition rod insulation skin is damaged, short circuit to the ground.

5, ignition cable and transformer failure: cable break, connector damage caused by short circuit when ignition; The transformer is disconnected or has other faults.

There are five treatment measures: clear, replace, adjust the distance, change the line, change the transformer.

Second, the ignition rod of the gas boiler has sparks but does not ignite

The reason:

1. The ventilation gap of the cyclone disk is blocked by carbon accumulation, and the ventilation is poor.

2, the oil nozzle is unclean, blocked or worn.

3. The damper setting Angle is too small.

4. The distance between the tip of the ignition rod and the leading edge of the oil nozzle is inappropriate (too prominent or indented).

5, Di an oil gun solenoid valve is blocked by debris (small oil gun).

6, the oil is too viscous flow is not easy or the filter system is blocked or the oil valve is not opened, so that the oil pump is insufficient to absorb oil and the oil pressure is low.

7. The filter screen of the oil pump is blocked.

8, the oil contains more water (boiling noise in the heater).

The treatment measures are: clear; First clean, if not new; Turn down the test; Adjust the distance (3~4mm is good); Remove and clean (clean parts with diesel); Check pipelines and oil filters, insulation equipment; Remove the screw outside the oil pump, carefully remove the outer cover, take out the oil net inside, and soak it with diesel oil; Test with new oil.